Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements x x 8.6.5.14.2 During the standing test, the elevator seeped down 4" in 2 minutes. Identify and correct the source of oil loss before the elevator can returned to service.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The alarm bell shall be operational on auxiliary power. 5/28/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 x x Phase 2 fire service shall be operational. Fixed 4/17/2020 - Re-Inspect set for 5/28/2020 - 7AM 5/28/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The in car emergency light shall be operational. 5/28/2020
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load