Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate in machine room. 12/29/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate on emergency 110v power or normal power. Repair or replace 7/13/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone not operable 10/7/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Light bulbs in cab need to be guarded to prevent injury to persons in the event of breakage. Open type "egg crate" panels should be replaced with solid panels or plastic tubes to cover bulbs. 12/29/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 x MACHINE ROOM DOOR MUST BE SELF CLOSING / SELF LOCKING. LOCK CAN NOT BE ABLE TO BE DISABLED AT ANY TIME. 7/13/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door must be self closing/locking. Lock cannot be disabled at any time
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Need to replace lighting to insure at least 10 foot candles of illumination at floor level anywhere in machine room. Lights must be guarded against breakage.
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV has not yet been tested after being wrote up last year. Elevator must have a category 5 weight test performed within 90 days. 7/13/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed, perform required test & seal on or before next anniversary date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 12/6/2018
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Replace broken light fixture in elevator cab. 10/23/2019
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)6 Replace cartop guide shoes to reduce post to post movement of elevator
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)6 x REPLACE CARTOP GUIDE SHOES TO REDUCE POST TO POST MOVEMENT OF ELEVATOR 7/13/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Replace lighting to insure at least 10 foot candles of illumination at floor level anywhere in machine room. Lights must be guarded against breakage
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) x REPLACE LIGHTING TO INSURE AT LEAST 10 FOOT-CANDLES OF ILLUMINATION AT FLOOR LEVEL ANYWHERE IN MACHINE ROOM. LIGHTS MUST BE GUARDED AGAINST BREAKAGE 7/13/2023