Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Emergency light and bell do not operate. 1/13/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x Smoke sensitive door reopening device does not disable on firefighter phase 2 operation. 14 days to fix issue or elevator will be red tagged. 11/16/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x x the infrared edge needs to be disabled on fire service recall 2/21/2022
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x the audible signal did not work on fire service recall 2/21/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation no mcp on site 2/18/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt. displayed 2/18/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate a new copy of the state certificate is to be posted in the machine room every year 2/18/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log monthly fire service test log is to be filled out and posted in the machine room 2/18/2024