Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) 1) Permanently installed electric lighting shall be provided in all machinery spaces, machine rooms, control spaces, and control rooms. 9/16/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops Clean the car top. 1/31/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current operating certificate shall be displayed in machine room. 8/30/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x During emergency power testing, car failed to recall to lobby. 1/30/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Maintenance control program shall be provided on site. 8/30/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Permanently installed lighting shall be provided in all machine spaces, including top of hoistway. 8/30/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate. 1/31/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 2.11 Provide hoistway door fire retainer, all floors. 1/31/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Provide testing of elevator on emergency power.. 9/28/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Provide testing of emergency generator selector switch. 9/28/2023
A17.1-2016 : Elevators 4.12 - Standby power selection switch 2.27.2 x Provide testing of the elevator emergency power selector switch in the lobby. 1/30/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 8.11.2.2.7 x Provide testing of the elevator emergency power selector switch. 1/17/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.2.7 x Provide testing of the elevator on emergency power. 1/17/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 8.6.4.5 x x Safeties set before the minimum required slide of 10 inches. Red tagged elevator. 6/6/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) There is no lighting in machine space on top of hoistway. 9/16/2019