Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The cab lighting shall be a minimum of 5 foot-candles. 7/13/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Cab lighting shall be a minimum of 5 ftc. 7/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x The door re-opening photo eyes do not work. 3/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Door reopening photo eye does not work. (2nd Notice) 7/13/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing and self-locking. 7/13/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-locking. 7/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Note: Only wiring diagrams are on-site. 7/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 7/13/2023