Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service test and post a log in the machine room 6/9/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Check valve is needing to be replaced, elevator settled 2 inches during 15 minute set test, it did not move at all when the machine room gate valve was closed 11/11/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Pit bucket is full of water. Need a new pit bucket and drain hose is rotted, replace drain hose 8/9/2024
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit, water and oil mixture on pit floor 8/9/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Replace or relabel the fire service phase 2 key switch collar, can no longer read the markings on the collar 8/9/2024