MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Check valve is needing to be replaced, elevator settled 2 inches during 15 minute set test, it did not move at all when the machine room gate valve was closed
|
11/11/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the pit, water and oil mixture on pit floor
|
8/9/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service test and post a log in the machine room
|
6/9/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Pit bucket is full of water. Need a new pit bucket and drain hose is rotted, replace drain hose
|
8/9/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Replace or relabel the fire service phase 2 key switch collar, can no longer read the markings on the collar
|
8/9/2024
|