MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
x
|
|
Hydraulic control valve in elevator pump unit is leaking fluid while running. Repair or replace hydraulic control valve. Re-inspection required
|
8/18/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Install a sleave to move the stop ring to prevent the car going to the top floor where the hatch door has been sealed and walled over on the lobby side
|
|
conversion
|
conversion
|
n/a
|
|
|
Move limits down so that elevator does not travel to blind hoistway covered by dry wall.
|
9/13/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service and document on log in the machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State certificate in machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair phone in car
|
12/7/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Repair pit light
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
The car top inspection light/fixture did not operate. Repair fixture/light for proper operation and illumination for maintenance/emergency personnel.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
The position indicating or “PI” device in the car was not operational on the day of inspection. Repair “PI” device to indicate the position of the elevator car.
|
|