MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test is incomplete, need to perform testing of emergency generator power operation to compete inspection. Re-inspection required
|
3/24/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm does not work. Re-inspection required
|
3/24/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light does not work. Re-inspection required
|
3/24/2026
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit has water in it, pit must remain clean & dry
|
3/11/2026
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency generator testing shall be performed. Re-inspection required
|
5/18/2024
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit has water in it, must remain clean & dry
|
3/1/2023
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Unable to perform testing of Emergency Generator power operation. Re-inspection required
|
|