Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)9 There is no protection found on this elevator power supply to prevent accidental motor phase reversal. Without a motor phase reversal device, there is a greater potential for equipment damage when a power loss occurs. Provide a motor phase reversal device on the elevator power supply. 6/11/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The lighting in the elevator machine room is not sufficient. The lighting shall not be less than (10) foot candles at the floor level. (noted on previous report) 3/6/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication is not working. Re-inspection required 1/12/2023