Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone in does not provide 2 way communication, needs repaired. Re-inspection required
conversion conversion n/a No No The machine room lighting was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. 9/12/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2017. 9/12/2019
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. 9/12/2019
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No The machine room lighting was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. 9/12/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Light in pit does not work, needs repaired