Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post Current Operating Certificate in Machine room 11/17/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Phase 1 does not recall the elevator to the recall floor when the elevator is switched from Phase II to Phase I 3/26/2025
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Provide working Phase 1 & Phase 2 fire service operation. 8/23/2019
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Post Phase 1 fire service instructions near the fire service switch. 8/23/2019
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Post Phase 2 fire service instructions near the fire service switch in the car. 8/23/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Governor Rope showing rope rouge and diameter is below maximum allowable amount 5/24/2023
MO Minimum : Elevators (I) - Pits (I)1 No No Clean hoistway and pit. Excessive powder and debris 4/16/2021
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. 5/21/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room ceiling is leaking. The leak shall be repaired. 5/21/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room door shall be self-closing. 5/21/2020
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No Remove the extension cord from the machine room window. 5/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The alarm ball does not work when normal power is removed 6/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.2 Replacement of Suspension Means (Re-Inspection) Yes No Suspension ropes are showing rouge and the diameter has reduced beyond the maximum allowable amount. Replace suspension ropes. 6/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Alarm bell does not work when normal power is removed 3/26/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No The in car emergency telephone shall be operational. 5/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Car top light shall work. 5/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Clean the car top. 5/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Provide a current tested fire extinguisher in the elevator machine room. 5/21/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) No No Telephone in car doesn't work. Phone line dead to elevator controller 4/16/2021