ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
The means to restrict opening of the car door shall be operational.
|
2/4/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The two-way communication means shall provide on demand to authorized personnel, information that identifies the building location and elevator number and that assistance is required. Note: The company monitoring the phone was not able to provide location information.
|
9/21/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be posted in the elevator machine room.
|
8/26/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
9/23/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
Emergency power operation of the elevators shall be tested as part of the annual inspection.
|
4/30/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
The GFI in the controller shall be operational.
|
8/26/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.11.2.1.3(w)
|
|
|
The missing door hall door guide at the 11th floor shall be replaced.
|
8/26/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.29 - Car and counterweight safeties
|
8.11.2.2.2
|
x
|
x
|
PERFORM 5-Year full load CAT 5 test. Re-Inspect within 30 days
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.3.5
|
x
|
|
Test emergency generator
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
8/26/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980)
|
8.6.11.1
|
|
|
Perform monthly fire service test and document on the log posted in the machine room.
|
3/12/2025
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. – 8.6.1.4 or 8.6.10.1
|
9/23/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11
|
x
|
|
Provide code compliant counterweight runby.
|
4/30/2021
|