A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Provide annual testing of elevators on emergency power.
|
2/23/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Provide MCP.
|
8/14/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display a current state operating certificate.
|
11/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
The pit lighting shall be operational.
|
11/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
The machine room door shall be self-locking.
|
11/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
12/15/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
The machine room lighting shall not be less than 10 ftc at the floor of the machine room.
|
11/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.13 - Emergency exit
|
2.14.1.5
|
|
|
Emergency exit cover switch shall be operable. Repair/replace same. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.13 - Emergency exit
|
2.14.1.5
|
x
|
|
Car top emergency exit not code compliant, make so.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.9 Cleaning of Car Tops
|
|
|
Clean the car top.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
Door restrictor out of adjustment, repair or replace as needed.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone works, but is requesting keypad entry, reprogram.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Provide Cat 1 testing of the elevator on emergency power.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.12 - Standby power selection switch
|
2.27.2
|
x
|
|
Provide Cat 1 testing of the emergency power selector switch.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in elevator was not answered, phone not working. Re-inspection required
|
2/2/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to provide testing of fire service to complete inspection. Re-inspection required
|
2/2/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Existing cab emergency telephone does not work and shall be repaired and tested.
|
5/30/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car emergency phone shall work.
|
5/8/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Independent riser push button on door buck has broken halo ring,repair as needed
|
8/14/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevator appears to have emergency generator power, which needs to be scheduled and tested. Re-inspection required
|
2/2/2024
|