Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display a current state operating certificate. 11/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits The pit lighting shall be operational. 11/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) The machine room door shall be self-locking. 11/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) The machine room lighting shall not be less than 10 ftc at the floor of the machine room. 11/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.13 - Emergency exit 2.14.1.5 Emergency exit cover switch shall be operable. Repair/replace same. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops Clean the car top.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Provide MCP. 8/14/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Independent riser push button on door buck has broken halo ring,repair as needed 8/14/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevator appears to have emergency generator power, which needs to be scheduled and tested. Re-inspection required 2/2/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x Door restrictor out of adjustment, repair or replace as needed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone works, but is requesting keypad entry, reprogram.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide Cat 1 testing of the elevator on emergency power.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 x Provide Cat 1 testing of the emergency power selector switch.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in elevator was not answered, phone not working. Re-inspection required 2/2/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to provide testing of fire service to complete inspection. Re-inspection required 2/2/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.13 - Emergency exit 2.14.1.5 x Car top emergency exit not code compliant, make so.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Provide annual testing of elevators on emergency power. 2/23/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Existing cab emergency telephone does not work and shall be repaired and tested. 5/30/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car emergency phone shall work. 5/8/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 12/15/2021