Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevator appears to have emergency generator power, which needs to be scheduled and tested. Re-inspection required 2/2/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to perform the following tests to complete inspection: unintended movement, fire service, emergency light & alarm, set safeties (no load). Re-inspection required 2/2/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevator appears to have emergency generator backup power, which needs to be scheduled and tested to complete inspection. Re-inspection required 2/20/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing Incomplete. Need to test: EP, F.S., Door#, CommLoss, 100%set, slide, UMup & UMdn, check MCP
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Elevator phone in car is not working. Re-inspection required 2/20/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone in car did not answer, needs repaired. Re-inspection required 2/2/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No In car emergency telephone shall work. 5/8/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No There is a hoistway door closing issue on the 1st floor. 12/15/2021
MO Minimum : Elevators (I) - Pits (I)1 No No Need to install warning sign on pit door stating "Caution Elevator Pit" 7/28/2025
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) No No Install cable data tag on car cable shackles 7/28/2025
A17.1-2016 : Elevators 3.17 - Door and gate equipment 2.12 No No Interlock at 11th floor shall have a proper cover(missing).
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) Yes No The car door restrictor shall be operational. 10/21/2021
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.2 Yes Yes Unintended Motion failed to limit the car travel to a maximum of 48" (Actual=67")in the down direction.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits No No The pit lighting shall be operational. 11/17/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Existing phone in car not working, no voltage. Repair as needed. 2/23/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Lobby indicator for phone line loss not working, repair as needed. 2/23/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display a current state operating certificate in the elevator machine room. 11/17/2022
A17.1-2016 : Elevators 3.23 - Suspension Means 8.10.2.2.3(cc) No No Hoist and Comp Ropes appear dry and showing beginning stages of “rouge”. Ropes shall be cleaned and lubricated per OEM recommendations.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The emergency phone shall be operational. 10/21/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Existing cab emergency telephone does not work and shall be repaired and tested. 5/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) No No The machine room door shall be self-locking. 11/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) No No The machine room lighting shall not be less than 10 ftc at the machine room floor. 11/17/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No Provide MCP. 8/14/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No The emergency lighting shall be operational. 10/21/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Provide annual testing of elevators on emergency power. 2/23/2023
A17.1-2016 : Elevators 3.27 - Crosshead data plate 8.7.2.17.3 Decrease in Rated Speed No No Hoist and Governor Ropes shall have appropriate data tags