Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements A current tested fire extinguisher is required in the machine room. 10/1/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 10/1/2023
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.14.5.7 x Door restrictor out of adjustment, repair as needed. 2/23/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevator appears to have emergency generator backup power, which needs to be scheduled and tested to complete inspection. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevator appears to have emergency generator power, which needs to be scheduled and tested. Re-inspection required 2/2/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in car was not answered, phone needs repaired. Re-inspection required 2/2/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Existing cab emergency telephone does not work and shall be repaired and tested. 6/24/2019
A17.1-2016 : Elevators 2.27 - Rope fastenings 8.11.2.1.2(cc) Install cable data tag on car shackles with correct size and type of rope
MO Minimum : Elevators (I) - Pits (I)3 Install counterweight guard. 10/1/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform testing of fire service to complete inspection. Re-inspection required 2/2/2024
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 1 & Phase 2 fire service shall be tested. (Phase 1 not working, Phase 2 could not be tested). 2/11/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Provide annual testing of emergency power selector switch. 2/23/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Provide MCP. 8/14/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Provide pit light. 10/1/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Provide testing of elevators on emergency power. 2/23/2023