Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 2/11/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 2/11/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) x Car door restrictor does not work. 3/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Elevator equipped with scavenger pump in pit that does not record the amount of oil returned to the hydraulic tank. Either install a recordable scavenger pump or limit the amount of oil stored in the pit to 5 gallons. 3/1/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room needs service - 2016 edition 2/11/2022
MO Minimum : Elevators (A) - Hoistways (A)13 x Hole on the back wall in the hoistway at the fourth floor needs to be patched. 3/10/2025
MO Minimum : Elevators (S) - Fire Service (S)1 x x On Phase II fire service, the call cancel button does not work. Repair and reinspect by 8-16-20 3/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Repair car door restrictor. 4/16/2021