MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
2/11/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
2/11/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
x
|
|
Car door restrictor does not work.
|
3/29/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Elevator equipped with scavenger pump in pit that does not record the amount of oil returned to the hydraulic tank. Either install a recordable scavenger pump or limit the amount of oil stored in the pit to 5 gallons.
|
3/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in machine room needs service - 2016 edition
|
2/11/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
x
|
|
Hole on the back wall in the hoistway at the fourth floor needs to be patched.
|
3/10/2025
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
On Phase II fire service, the call cancel button does not work. Repair and reinspect by 8-16-20
|
3/29/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Repair car door restrictor.
|
4/16/2021
|