Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code A machine room light fixture was not operational on the day of inspection. Repair light fixture for proper illumination for maintenance and emergency personnel.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 9/11/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone now working. 11/8/2018
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair pit light. 1/20/2021
A17.1-1996 : Elevators 1.8 - Door closing force 1001.2(a)(8) x The elevator car door closing force is over the maximum allowable force of 30lbs. Readjust door closing force to be less than 30lbs. Reinspection required. 6/20/2022
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 202 x The left bottom counterweight guide roller needs to be replaced. 9/11/2019
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 1001.2(c)(13) There is a bottom guide roller on the counterweight that has deteriorated and shall be replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits.