MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
x
|
|
Car door restrictor does not work.
|
5/18/2020
|
conversion
|
conversion
|
n/a
|
|
|
Door closing force shall be less than 30#
|
11/8/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency light and bell shall work
|
8/15/2018
|
conversion
|
conversion
|
n/a
|
|
|
Failed static test, leaking back through control valve
|
11/8/2018
|
conversion
|
conversion
|
n/a
|
|
|
Fire stops on hoistway doors are missing
|
11/8/2018
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Phase 2 fire service does not work correctly. When at alternate landing and Phase 2 switch is moved from On to Hold, door closes and reverts back to Phase 1. Did not red tag. Reinspect within 30 days.
|
5/18/2020
|