Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Emergency alarm and light not not work when 110 AC removed 9/30/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency Light and Bell do not work when normal power is removed. When the missing fuse is replaced, the bell rings constantly. 10/6/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements x x During full load Safeties Test, Safeties stopping distance measures 5" and the minimum for a 450fpm car is 11" 8.6.4.20.1 10/6/2022