Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Alarm bell on left hand Car Operating Panel when button or Stop switch is pressed 11/28/2022
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x One of two emergency lamps is not working (right-hand COP). 6/26/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine room lighting is less than the required 19fc at controller. 6/26/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Machine room outlets are not GFCI protected. 6/26/2024
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.5 Wedge Rope Sockets x Hoist Rope Tail retaining clips shall be properly spaced. 6/26/2024
A17.1-2016 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 2.10.2.3 Toe Board x Cartop needs 4" toe kick around perimeter under handrails. 6/26/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.6 x Pit stop switch to be reachable from access door. 6/26/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit lighting is less than the required 10fc. 6/26/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 3.26.1 x Mainline disconnect failed to trip when heat detector is activated. 6/26/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27.1 Phase I Emergency Recall Operation After Device Actuation x x Main floor smoke sent elevator to main floor. 6/26/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test fire service phase 1 & 2. 6/26/2024
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x One of two emergency lamps is not working (right-hand COP). 3/21/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine room lighting is less than the required 19fc at controller. 3/21/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Machine room outlets are not GFCI protected. 3/21/2025
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.5 Wedge Rope Sockets x Hoist Rope Tail retaining clips shall be properly spaced. 3/21/2025
A17.1-2016 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 2.10.2.3 Toe Board x Cartop needs 4" toe kick around perimeter under handrails. 3/21/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit lighting is less than the required 10fc. 3/21/2025