MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
|
|
Alarm bell on left hand Car Operating Panel when button or Stop switch is pressed
|
11/28/2022
|
A17.1-2016 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.10.2.3 Toe Board
|
x
|
|
Cartop needs 4" toe kick around perimeter under handrails.
|
6/26/2024
|
A17.1-2016 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.10.2.3 Toe Board
|
x
|
|
Cartop needs 4" toe kick around perimeter under handrails.
|
3/21/2025
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.5 Wedge Rope Sockets
|
x
|
|
Hoist Rope Tail retaining clips shall be properly spaced.
|
6/26/2024
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.5 Wedge Rope Sockets
|
x
|
|
Hoist Rope Tail retaining clips shall be properly spaced.
|
3/21/2025
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Machine room lighting is less than the required 19fc at controller.
|
6/26/2024
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Machine room lighting is less than the required 19fc at controller.
|
3/21/2025
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Machine room outlets are not GFCI protected.
|
3/21/2025
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Machine room outlets are not GFCI protected.
|
6/26/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
3.27.1 Phase I Emergency Recall Operation After Device Actuation
|
x
|
x
|
Main floor smoke sent elevator to main floor.
|
6/26/2024
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
3.26.1
|
x
|
|
Mainline disconnect failed to trip when heat detector is activated.
|
6/26/2024
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
x
|
|
One of two emergency lamps is not working (right-hand COP).
|
3/21/2025
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
x
|
|
One of two emergency lamps is not working (right-hand COP).
|
6/26/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Pit lighting is less than the required 10fc.
|
6/26/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Pit lighting is less than the required 10fc.
|
3/21/2025
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.6
|
x
|
|
Pit stop switch to be reachable from access door.
|
6/26/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test fire service phase 1 & 2.
|
6/26/2024
|