MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Accumulated oil in pit
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
All applicable FAID will be tested with all 5 tractions cars online.
|
3/21/2025
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.9
|
x
|
|
Controller code data plate is blank.
|
3/21/2025
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
Emergency communication failure detection system shall work.
|
3/21/2025
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power to be tested with rated load.
|
3/21/2025
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Machine room 4x4 box shall have wiring inside box and cover installed.
|
3/21/2025
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
2.29.1
|
x
|
|
Machine room machinery, controllers, governors, disconnects, etc. shall have proper numbering.
|
3/21/2025
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Machine room outlests to be GFI protected.
|
3/21/2025
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove oil from pit floor
|
|
A17.1-2016 : Elevators
|
5.6 - Governor-rope tension devices
|
2.18.7
|
x
|
|
Shorten governor rope to allow proper pit clearance of tail-sheave. Currently only about 1/2" clearance to pit floor.
|
3/21/2025
|