MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Car safeties will not set ar full speed with full load. Governor rope slides through governor jaws
|
8/2/2019
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Phase II fire service doesn't work
|
8/2/2019
|
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.2.3
|
x
|
x
|
The when tripping the governor with full load at rated speed, The governor rope slides through the governor jaw, and the safeties do not engage.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
5-year testing incomplete. Need to perform Emergency Light/Phone backup power test, full loaf safeties set, and Fire Service test.
|
|