Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Lower door reopening device shall work. 11/8/2018
MO Minimum : Elevators (I) - Pits (I)1 Elevator pit is full of water. 6/10/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light does not work. 5/18/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x Phase 2 fire service does not work correctly. When at alternate landing and Phase 2 switch is moved from On to Hold, door closes and reverts back to Phase 1. Did not red tag. Reinspect within 30 days. 5/18/2020
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit shall be cleaned of dirt and debris. 10/13/2020
MO Minimum : Elevators (I) - Pits (I)8 The sump pump hole in the pit shall be provided with a noncombustible cover that is flush with the pit floor. The current cover provided shall be modified to to cover sump hole. 10/13/2020