Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Elevators connected to an emergency generator shall be tested for operation on emergency power. Re-inspection required 3/4/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Tried to perform elevator emergency power test, elevator would not run on emergency power. Also ensure that the elevator cab lights are on emergency power. Re-inspection required 8/9/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Tried to perform elevator emergency power test. Elevator would not run on emergency power. Also ensure that elevator cab lights are on emergency power. Re-inspection required 8/30/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Test phase 1 and 2 fire service. Re-inspection required 3/4/2024