Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Piping for pit lights and receptacle is rusted through, wire is exposed. Replace rusted out pipe and boxes. 5/20/2024
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 No No Provide / fill in crosshead data tag, change tag speed to 150 fpm 5/20/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.15 - Static control 2.62.2 No No Unit has a scavenger pump in the pit. The pump shall be removed and replaced with an appropriate bucket so that oil loss can be recorded
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.5.7 Record of Oil Usage No No Unit has a scavenger pump in the pit. The pump shall be removed and replaced with an appropriate bucket so that oil loss can be recorded 5/19/2025