Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No Emergency power shall be tested. 8/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No -Emergency Phone in car fails to establish two-way communication 11/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No 210.8 The brake switches are not working. The elevator will run regardless of the position of the brake. 12/6/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes Yes 8.6.4.6 The main brake is not opening when the elevator runs. The elevator is running through the brake 12/6/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors Yes No There are holes appearing in the platform flooring from excessive corrosion. Repair platform flooring with appropriate fire rated material. 12/6/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The Emergency Phone in the car fails to establish two-way communication. 11/16/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display the current state operating certificate. 11/16/2025
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No The cab lighting shall be properly guarded to prevent accidental contact or breakage. 11/16/2025
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No Provide Firemans Return Phase 1 instructions in the lobby near the key switch. 11/16/2025
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The pit shall be kept clean. 11/16/2025
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No The pit light switch shall be accessible from the hoistway door. 11/16/2025
A17.1-1996 : Elevators 1.14 - Ventilation 1001.2(a)(14) No No The cab ventilation fan shall be operational. 11/16/2025