Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x -Emergency Phone in car fails to establish two-way communication 1/24/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication 2/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication
MO Minimum : Elevators (I) - Pits (I)1 All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator.
A17.1-1996 : Elevators 1.14 - Ventilation 1001.2(a)(14) The cab ventilation fan shall be operational.
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Emergency power shall be tested. 8/16/2021
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x The front and rear door restrictors shall be operational. 8/16/2021
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 1001.2(c)(13) x Replace the bad counterweight roller on the bottom of frame. 8/16/2021
A17.1-1996 : Elevators 4.2 - Hoistway doors 1001.2(d)(2) Provide a sight guard on the lobby door.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 A pit light shall be provided.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit shall be kept clean.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 The cab lighting shall be properly guarded to prevent accidental contact or breakage.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Provide Firemans Return Phase 1 instructions in the lobby near the key switch.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display the current state operating certificate.