Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 The elevator car door closing force is over the maximum allowable force of 30lbs. Readjust door closing force to be less than 30lbs.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. 12/7/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency car lighting has only one light bulb fixture operational.The light bulb fixture shall be repaired to operate. Reinspection required. 12/7/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x In phase II operation, the elevator car will not override the security feature on the car operating panel. Security shall be overridden in fireman’s service. 12/7/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
conversion conversion n/a The securing latches on the car operating panel in the car are broken and will not keep the panel in the closed position resulting in a possible electrical hazard. The securing latches shall be repaired or replaced. 11/7/2018