conversion
|
conversion
|
n/a
|
|
|
The elevator pit floor is covered in oil. The elevator pit shall be kept clean and dry.
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
The hydraulic cylinder gland packing is leaking excessively and shall be replaced.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
x
|
|
The pit has a scavenger pump unit in it for oil loss collection. This scavenger pump does not allow for accurate oil loss for proper documentation of an oil loss log. Scavenger pump shall be removed and replaced with a 5 gallon bucket so that a log can be properly kept. Reinspect in 30 days
|
12/11/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
There is a oil recovery unit installed in the pit of this elevator designed to return the oil leakage from the packing gland on the cylinder head. The State of Missouri has determined that this device does not suffice for oil leakage and is only allowed for temporary use until the packing gland can be repaired/replaced. Remove the recovery unit after the packing gland has been repaired/replaced and record the oil loss per A17.1 2016 - 8.6.5.5.7
|
|