Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Oh phase 2 fire service, the hold position on the key switch is not functional, needs repaired. Re-inspection required 2/21/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Elevators connected to an emergency generator shall be tested for operation on emergency power. Re-inspection required 2/21/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x The emergency power generator did not initiate as required to perform the required test. Reinspection and test is required. 7/29/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Repair car door restrictor 12/9/2019
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Door restrictors must be operational 4/29/2021
A17.1-1996 : Elevators 2.4 - Machine space 100.3d Remove waterhose running through machine room 10/7/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 10/7/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the machine room 12/22/2022