Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No The fire extinguisher shall be up to date.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No The in car alarm bell shall be operational on main and on auxiliary power. The alarm bell intermittently fails to operate when the button is pushed.
MO Minimum : Elevators (A) - Hoistways (A)16 No No A cover is missing on a conduit body in the hoistway at the top floor, it shall be replaced.
MO Minimum : Elevators (A) - Hoistways (A)16 No No The electrical fitting on gate switch is broken and shall be replaced.
MO Minimum : Elevators (F) - Electrical Switches (F)2 Yes No The upper final limit shall be operational. 7/13/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. 9/10/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Install anti-rotation device on the counterweight shackles. 9/10/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 9/10/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide a code compliant MCP including onsite documents. 1/31/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be displayed in the elevator machine room. 1/31/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/15/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. 3/15/2024