Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation 7th floor push button needs to be replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Category 5 weight testing has not been performed since 2016. Category 5 testing shall be performed and witnessed immediately.
MO Minimum : Elevators (I) - Pits (I)3 Compensating chains need to be shortened.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing and self-locking. Mechanic stated the lock jams from the inside.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Machinery, controllers, governors, disconnects shall be numbered conspicuously. Governors are not numbered.
MO Minimum : Elevators (J) - Counterweights (J)1 Negative counterweight runby, remove counterweight blocking.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Repair inoperative emergency lights. 11/19/2024
MO Minimum : Elevators (S) - Fire Service (S)1 x Restore door operation and re-test fire service. 11/15/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Suspension means shall have proper data tags.