Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing and self-locking. Door was found unlocked and unlatched.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Category 5 weight testing has not been performed since 2016. Category 5 testing shall be performed and witnessed immediately.
conversion conversion n/a Fire extinguisher needs to be serviced 11/13/2020
conversion conversion n/a There shall be pull straps at all floors inside and outside each hall door. 11/13/2020
conversion conversion n/a We also completed 5-yr. safety test. Put 10000 pounds on car and set safeties. The slide was of 3 inches. 11/13/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.