MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Category 5 weight testing has not been performed since 2016. Category 5 testing shall be performed and witnessed immediately.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self-closing and self-locking. Door was found unlocked and unlatched.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2 On-Site Documentation
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
conversion
|
conversion
|
n/a
|
|
|
Fire extinguisher needs to be serviced
|
11/13/2020
|
conversion
|
conversion
|
n/a
|
|
|
There shall be pull straps at all floors inside and outside each hall door.
|
11/13/2020
|
conversion
|
conversion
|
n/a
|
|
|
We also completed 5-yr. safety test. Put 10000 pounds on car and set safeties. The slide was of 3 inches.
|
11/13/2020
|