Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The following tests need to be performed to complete 5 year inspection: full load, full speed car safeties, full load, full speed car buffer, counterweight safeties, 125% brake, overspeed governor jaw and switch speeds, overspeed governor pull thru, safeties pull out. Re-inspection required 2/26/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The following tests need to be performed to complete 5 year inspection: full load, full speed car safeties, full load, full speed car buffer, counterweight safeties, 125% brake, overspeed governor jaw and switch speeds, overspeed governor pull thru, safeties pull out. Re-inspection required 3/27/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. Re-inspection required 2/26/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Repair door knob in machine room. 10/19/2020
MO Minimum : Elevators (I) - Pits (I)1 Drain standing water from pit. 1/4/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Hoist ropes are showing signs of wear and stretching, need to replace the ropes within 60 days. Re-inspection required 2/26/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 3/11/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room 3/11/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated operating certificate in machine room. 10/19/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate. 1/28/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No monthly fire log. 1/28/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Elevator lost traction before actuating top final limit switch. Red-tagged, Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Safety actuating arm appears to strike pit equipment when running down onto bottom final limit switch, repair same. Re-inspection required