conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Repair car door restrictor
|
8/8/2019
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current operating certificate.
|
1/27/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
No monthly fire log.
|
1/27/2020
|
conversion
|
conversion
|
n/a
|
|
|
Clean elevator car top.
|
1/27/2020
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Hoist ropes need to be shortened. 15 days to complete repair and reinspect.
|
2/7/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Repair broken Greenfield to top of car exit switch.
|
10/19/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display updated operating certificate in machine room.
|
10/19/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Machine room shall be kept clean.
|
10/19/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
3/11/2024
|
A17.1-2016 : Elevators
|
2.25 - Traction sheaves
|
8.6.4.20.10 Braking System, Traction, and Traction Limits (Re-Inspection)
|
x
|
x
|
When performing the 5 year test, the car is loaded with 125% of the rated load. This requires testing to ensure that the car will safely stop and hold the load with the car leveled with the floor. During testing the traction sheave slipped and failed the 125% test. The elevator is placed out of service and a repair/reinspection shall be performed before the elevator is returned to operation.
|
4/9/2024
|