Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.25 - Traction sheaves 8.6.4.20.10 Braking System, Traction, and Traction Limits (Re-Inspection) x x When performing the 5 year test, the car is loaded with 125% of the rated load. This requires testing to ensure that the car will safely stop and hold the load with the car leveled with the floor. During testing the traction sheave slipped and failed the 125% test. The elevator is placed out of service and a repair/reinspection shall be performed before the elevator is returned to operation. 4/9/2024
conversion conversion n/a Clean elevator car top. 1/27/2020
conversion conversion conversion - reinspect x Repair car door restrictor 8/8/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate. 1/27/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No monthly fire log. 1/27/2020
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Hoist ropes need to be shortened. 15 days to complete repair and reinspect. 2/7/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Repair broken Greenfield to top of car exit switch. 10/19/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated operating certificate in machine room. 10/19/2020
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine room shall be kept clean. 10/19/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 3/11/2024