MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
3/11/2024
|
conversion
|
conversion
|
n/a
|
|
|
Clean elevator car top.
|
1/27/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current operating certificate.
|
1/27/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display updated operating certificate in machine room.
|
10/19/2020
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Hoist ropes need to be shortened. 15 days to complete repair and reinspect.
|
2/7/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Machine room shall be kept clean.
|
10/19/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
No monthly fire log.
|
1/27/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Repair broken Greenfield to top of car exit switch.
|
10/19/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Repair car door restrictor
|
8/8/2019
|
A17.1-2016 : Elevators
|
2.25 - Traction sheaves
|
8.6.4.20.10 Braking System, Traction, and Traction Limits (Re-Inspection)
|
x
|
x
|
When performing the 5 year test, the car is loaded with 125% of the rated load. This requires testing to ensure that the car will safely stop and hold the load with the car leveled with the floor. During testing the traction sheave slipped and failed the 125% test. The elevator is placed out of service and a repair/reinspection shall be performed before the elevator is returned to operation.
|
4/9/2024
|