Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 12/15/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x The selector cable is frayed and shall be replaced. - Unit Red Tagged. 4/15/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. 12/15/2023
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. 12/15/2023
MO Minimum : Elevators (H) - Machine Rooms (H)1 Stairwell leading to machine room has insufficient lighting. It must be at least 19 foot-candles. 12/19/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The lighting in the machine room shall be not less than 10 foot-candles at the floor level. 12/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x x The emergency light, alarm, and phone shall be operational. Unit Red Tagged. 4/15/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 12/15/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 The escape hatch is missing a cover. 6/15/2021