A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone rings to 911. Reprogram and retest.
|
6/18/2021
|
A17.1-1996 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
303
|
|
|
Hydraulic fitting under the hydraulic valve appears to be worn and leaking oil on top of the tank. Repair or replace
|
12/7/2023
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide on-site written maintenance control program for each elevator.
|
12/7/2023
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV is not sealed and noted on last inspection report of 2020. Perform OSV test within 90 days.
|
7/29/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current certificate.
|
12/7/2023
|