MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
x
|
|
Door restrictor doesn't work
|
12/5/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not dial out
|
9/26/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency Phone in car fails to establish two-way communication (Busy Signal)
|
9/12/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
The suspension ropes need to seat to the same depth in the drive sheave grooves. Two of the ropes are sitting lower in the grooves of the drive sheave.
|
9/12/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
x
|
Emergency phone is not operational since 2022. Elevator Red Tagged.
|
9/18/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
The suspension ropes need to seat to the same depth in the drive sheave grooves. Two of the ropes are sitting lower in the grooves of the drive sheave. Note: This violation was cited during an alteration inspection on 5/22/2024 and is still not corrected.
|
9/18/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communications/phone is car shall be operational. This violation shall be corrected within 14 days.
|
11/13/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2 On-Site Documentation
|
|
|
A current MCP shall be provided in the machine room including maintenance, repair, testing and fire service testing logs.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Excessive amount of debris and trash in pit
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Doors stay open at floors during Phase II operation.
|
12/13/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Phase II fire service - Doors don't stay open when car is at another floor
|
12/5/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Phase II fire service - "HOLD'' doesn't work
|
12/5/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
A slide measurement shall be obtained. Unable to test due to car being unable to pick capacity.
|
9/18/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
x
|
Unable to finish category 5 full load test. Unit failed to pick capacity. Elevator Red Tagged
|
9/18/2024
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Will not reset when Phase I is turned off
|
11/9/2018
|
conversion
|
conversion
|
n/a
|
|
|
Repair machine room door to be self closing and locking
|
2/24/2021
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Doors don't stay open on Phase II fire service when car is at another floor
|
11/9/2018
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|