Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) Yes No Door restrictor doesn't work 12/5/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not dial out 9/26/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall be operational.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit No No Excessive amount of debris and trash in the pit shall be cleaned.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A current MCP shall be provided in the machine room including maintenance, repair, testing and fire service testing logs.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A current MCP shall be provided in the machine room including maintenance, repair, testing and fire service testing logs.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Phone in car fails to establish two-way communication (Busy Signal) 9/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Yes No The suspension ropes need to seat to the same depth in the drive sheave grooves. Two of the ropes are sitting lower in the grooves of the drive sheave. 9/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes Yes Emergency phone is not operational since 2022. Elevator Red Tagged. 9/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Yes No The suspension ropes need to seat to the same depth in the drive sheave grooves. Two of the ropes are sitting lower in the grooves of the drive sheave. Note: This violation was cited during an alteration inspection on 5/22/2024 and is still not corrected. 9/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency communications/phone is car shall be operational. This violation shall be corrected within 14 days. 11/13/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation No No A current MCP shall be provided in the machine room including maintenance, repair, testing and fire service testing logs. 6/5/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door shall be self closing, self locking, and shall be operable from the interior space without a key.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Yes No Pit light shall work.
MO Minimum : Elevators (I) - Pits (I)1 No No Excessive amount of debris and trash in pit 6/5/2026
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Doors stay open at floors during Phase II operation. 12/13/2019
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Phase II fire service - Doors don't stay open when car is at another floor 12/5/2019
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Phase II fire service - "HOLD'' doesn't work 12/5/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No A slide measurement shall be obtained. Unable to test due to car being unable to pick capacity. 9/18/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes Yes Unable to finish category 5 full load test. Unit failed to pick capacity. Elevator Red Tagged 9/18/2024
conversion conversion conversion - reinspect Yes No Will not reset when Phase I is turned off 11/9/2018
conversion conversion n/a No No Repair machine room door to be self closing and locking 2/24/2021
conversion conversion conversion - reinspect Yes No Doors don't stay open on Phase II fire service when car is at another floor 11/9/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/5/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.