Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Excessive amount of debris and trash in pit
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation A current MCP shall be provided in the machine room including maintenance, repair, testing and fire service testing logs.
conversion conversion conversion - reinspect x Will not reset when Phase I is turned off 11/9/2018
conversion conversion conversion - reinspect x Doors don't stay open on Phase II fire service when car is at another floor 11/9/2018
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase II fire service - Doors don't stay open when car is at another floor 12/5/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase II fire service - "HOLD'' doesn't work 12/5/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) x Door restrictor doesn't work 12/5/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x x Doors stay open at floors during Phase II operation. 12/13/2019
conversion conversion n/a Repair machine room door to be self closing and locking 2/24/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone does not dial out 9/26/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication (Busy Signal) 9/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x The suspension ropes need to seat to the same depth in the drive sheave grooves. Two of the ropes are sitting lower in the grooves of the drive sheave. 9/12/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Unable to finish category 5 full load test. Unit failed to pick capacity. Elevator Red Tagged 9/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x x Emergency phone is not operational since 2022. Elevator Red Tagged. 9/18/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x A slide measurement shall be obtained. Unable to test due to car being unable to pick capacity. 9/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x The suspension ropes need to seat to the same depth in the drive sheave grooves. Two of the ropes are sitting lower in the grooves of the drive sheave. Note: This violation was cited during an alteration inspection on 5/22/2024 and is still not corrected. 9/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency communications/phone is car shall be operational. This violation shall be corrected within 14 days. 11/13/2024