Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The category 5 portion of the required tested was completed at the time of the hoist/governor rope replacement inspection. The category 1/annual testing items shall be witnessed to complete the annual inspection.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone has no been working since 2022 was not working still at time of hoist/governor rope replacement inspection. The phone shall be made operational by 10/10/25 or the elevator will be red tagged again.
conversion conversion n/a Door restrictor doesn't work 2/24/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone does not dial out 9/26/2022
MO Minimum : Elevators (I) - Pits (I)1 Excessive amount of debris and trash in pit 9/26/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication (Busy Signal) 9/12/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Lights in elevator cab shall be guarded to prevent breakage 10/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete. Need to complete annual and category 5 test. Only tested emergency phone, bell, and light. 10/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x After entering the car top it was discovered the hoist ropes and governor rope failed the gauge test. Hoist rope and governor rope shall be replaced. Elevator Red Tagged. 10/8/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x x Emergency phone is not operational since 2022. Elevator Red Tagged. 10/8/2025