Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 Yes No Back of cab needs refastened.. 3/20/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 Yes No Clean Machine Room 3/20/2023
conversion conversion n/a No No Clean up the pit. 5/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(b) On-Site Maintenance Records (Repair and Replacement Records) No No NO records 2/9/2022
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 No No No-- Do Not Use Elevator in CASE OF FIRE signs posted 2/9/2022
conversion conversion n/a No No Obtain and display a current state operating certificate in the machine room. 5/21/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Obtain and display a current state operating certificate in the machine room. This was on last years inspection too. 5/21/2020
conversion conversion n/a No No Provide a 6 foot high chain link fence around the elevator equipment with a 36 inch wide gate that is always locked from the outside and never locked from the inside, it is to be self closing self latching. maintain a minimum of 36 inches clear working area in front of the equipment. 5/21/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Provide a 6 foot high chain link fence seperating the elevator equipment from the other building related equipment. I t is to be provided with a 3 foot wide gate with a self closing and self latching, locking system. This was on last years inspection too. 5/21/2020
conversion conversion n/a No No Provide phase 1 fire instructions at the primary landing 5/21/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Replace the burnt out light tubes in the light fixture above the controller in the machine room 5/21/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Replace the burnt out pit light. 5/21/2020