Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.14 - Ventilation 2.14.2.3 No No Car fan not properly installed. 8/28/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.14 - Ventilation 8.11.2.1.1(n) No No The ventilation fan has been replaced from the original and now has a substantial gap between the mounting. This installation does not conform to A17.1 2.14.1.6 and 8.6.2.1 as required. 8/28/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.14 - Ventilation 2.14.2.3 No No The ventilation fan has been replaced from the original and now has a substantial gap between the mounting. This installation does not conform to A17.1 2.14.1.6 as required. 8/28/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.14 - Ventilation 2.14.2.3 No No The ventilation fan has been replaced from the original and now has a substantial gap between the mounting. This installation does not conform to A17.1 2.14.1.6 as required. 8/28/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The elevator ADA telephone inside the elevator would not activate with the 110V disconnect in the machine room in the “off” position indicating that the battery had been depleted. Replaced the battery of this phone for proper operation and passenger safety. Reinspection required. 7/20/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The elevator ADA telephone inside the elevator would not activate with the 110V disconnect in the machine room in the “off” position indicating that the battery had been depleted. Replaced the battery of this phone for proper operation and passenger safety. Reinspection required. 8/28/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. 8/28/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Cable guard,back side of hoist motor missing. Replace. 8/28/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams No No Car top GFCI outlet not working, make so. 8/28/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean the car top. 8/28/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No The elevator car top shall be cleaned of dust and debris. 8/28/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. 8/28/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. 8/28/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) No No Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits. 8/28/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Provide existing emergency lights to work, bell was ok. 6/28/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Provide Phase II testing, record results. Car kept releveling unable to leave lobby. 14 days to repair. 6/28/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 30 days of inspection. Alteration permit and reinspection required. 8/28/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a machine room inspection was performed, a full inspection shall be performed before the annual is completed. Reinspection is required. 7/14/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a machine room inspection was performed, a full inspection shall be performed before the annual is completed. Reinspection is required. 9/9/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time. The elevator was out of service and only a visual inspection could be performed. 10/2/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time. The fireman’s service phase 1 and 2 shall be performed, and emergency/standby power tested before the inspection is completed. 8/28/2026