ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
11/25/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Display current state operating certificate.
|
10/15/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
: Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. No Certificate displayed. REPEAT VIOLATION, incorrectly marked compliant.
|
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Verify if 5 year full load test was performed on life jacket, if not done, perform test.
|
10/3/2018
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Replace junction box cover on pump unit with proper cover.
|
10/3/2018
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
No
|
No
|
Fire service emergency operation shall be tested monthly and a testing log shall be kept on-site.
|
10/15/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
No
|
No
|
Fire Service must be tested and properly documented monthly on Log Sheet located in the MCP, 2 of 5 previous months in 2026 have been documented.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
8.11.2.1.5(j)
|
Yes
|
Yes
|
Perform Category 5 test on life jacket.
|
7/26/2018
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
No
|
No
|
The pit shall be kept clean, dry, and free of oil and debris.
|
10/3/2018
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
MCP is not present in the machine room at this time.
|
7/24/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
Code compliant maintenance records shall be available on-site.
|
10/15/2019
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
No
|
No
|
OSV shall have current testing tag. Unit last had a category 5 test in 2018. A category 5 test is due on the overspeed valve on or before the next annual inspection.
|
8/14/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
2-way communication device shall give proper location message, Responding Agent could not provide location or elevator number.
|
|